EL6751-0010 | EtherCAT Terminal, 1-channel communication interface, CANopen, slave

EL6751-0010 | EtherCAT Terminal, 1-channel communication interface, CANopen, slave

EL6751-0010 | EtherCAT Terminal, 1-channel communication interface, CANopen, slave

Status LEDs
Fieldbus connection
Top view 
EL6751-0010 | EtherCAT Terminal, 1-channel communication interface, CANopen, slave

EL6751-0010 | EtherCAT Terminal, 1-channel communication interface, CANopen, slave

The terminal enables integration into an existing CANopen network in the EtherCAT terminal network. The EL6751-0010 is a CANopen slave and can be configured almost anywhere within the CANopen specification via EtherCAT.

Product status:

regular delivery

Product information

Technical dataEL6751-0010
TechnologyCANopen slave terminal
FieldbusCANopen
Number of fieldbus channels1
Data transfer rates10, 20, 50, 100, 125, 250, 500, 800, 1000 kbaud
InterfacesD-sub connector, 9-pin according to CANopen specification, galvanically decoupled
CommunicationCANopen network master and CANopen manager, optionally CANopen slave
Bus devicemax. 127 slaves
Hardware diagnosticsstatus LEDs
Current consumption E-bustyp. 230 mA
Special featuresstatus LEDs, CANopen slave
Weightapprox. 70 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataEL-24
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)24 mm x 100 mm x 52 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking
Wiringspecific push-in connection