SoltarFixarFechar

KL3202 | Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit

Image similar, may contain optional accessories
KL3202 | Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit

KL3202 | Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit

Run LED 1
Error LED 1
Run LED 2
Error LED 2
+R1
RL1
-R1
Shield
+R2
RL2
-R2
Shield
Top view 
Contact assembly 
KL3202 | Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit

KL3202 | Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit

The KL3202 analog input terminal allows resistance sensors to be connected directly. The Bus Terminal’s circuitry can operate the sensors using 2-wire or 3-wire connection techniques. Linearization over the full temperature range is realized with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminal's standard setting is: resolution 0.1°C in the temperature range of Pt100 sensors in 3-wire connection. The run LEDs give an indication of the data exchange with the Bus Coupler. The error LEDs indicate sensor faults (e.g. a broken wire).

Product status:

regular delivery

Product information

Technical dataKL3202
Number of inputs2
Power supplyvia the K-bus
Technology2-/3-wire
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ)
Measuring range-200…+850°C (Pt sensors); -60…+250°C (Ni sensors)
Connection method2- or 3-wire (default: 3-wire)
Conversion time~ 250 ms
Measuring currenttyp. 0.5 mA
Resolution0.1°C per digit
Measurement error/uncertainty< ±1°C
Electrical isolation500 V (K-bus/signal voltage)
Current consumption power contacts– (no power contacts)
Current consumption K-bustyp. 60 mA
Bit width in the process imageinput: 2 x 16 bit data (2 x 8 bit control/status optional)
Configurationno address setting, configuration via Bus Coupler or controller
Special featuresopen-circuit recognition
Weightapprox. 70 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx, DNV GL
Pluggable wiringfor all KSxxxx Bus Terminals
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataKL-12-8pinKS-12-8pin
Design formcompact terminal housing with signal LEDsterminal housing with pluggable wiring level
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
s*: 0.08…1.5 mm²,
st*: 0.08…1.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
s*: AWG28…16,
st*: AWG28…16,
f*: AWG26…16
Stripping length8…9 mm9…10 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule

Ordering information
KL3202Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit
KS3202Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit, pluggable wiring
KL3202-0010Bus Terminal, 2-channel analog input, temperature, RTD (Pt200), 16 bit
KL3202-0011Bus Terminal, 2-channel analog input, temperature, RTD (Pt200), 16 bit, Siemens S5 format
KL3202-0012Bus Terminal, 2-channel analog input, temperature, RTD (Pt500), 16 bit
KL3202-0013Bus Terminal, 2-channel analog input, temperature, RTD (Pt500), 16 bit, Siemens S5 format
KL3202-0014Bus Terminal, 2-channel analog input, temperature, RTD (Pt1000), 16 bit
KL3202-0015Bus Terminal, 2-channel analog input, temperature, RTD (Pt1000), 16 bit, Siemens S5 format
KL3202-0016Bus Terminal, 2-channel analog input, temperature, RTD (Ni100), 16 bit
KL3202-0017Bus Terminal, 2-channel analog input, temperature, RTD (Ni100), 16 bit, Siemens S5 format
KL3202-0020Bus Terminal, 2-channel analog input, temperature, RTD (0…1.2 kΩ), 16 bit
KL3202-0021Bus Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit, Siemens S5 format
KL3202-0023Bus Terminal, 2-channel analog input, temperature, RTD (Ni120), 16 bit
KL3202-0024Bus Terminal, 2-channel analog input, temperature, RTD (Ni120), 16 bit, Siemens S5 format
KL3202-0025Bus Terminal, 2-channel analog input, temperature, RTD (Ni1000), 16 bit
KL3202-0026Bus Terminal, 2-channel analog input, temperature, RTD (Ni1000), 16 bit, Siemens S5 format
KL3202-0027Bus Terminal, 2-channel analog input, temperature, RTD (10…10 kΩ), 16 bit
KL3202-0028Bus Terminal, 2-channel analog input, temperature, RTD (-40…+128°C), 16 bit, increased resolution 0.01°C
KL3202-0029Bus Terminal, 2-channel analog input, temperature, RTD (Ni1000), per Landis&Staefa, 16 bit