The Terminal enables within an EtherCAT Terminal network the integration of any DeviceNet devices and can either be master (EL6752) or slave (EL6752-0010). The DeviceNet terminal has a powerful protocol implementation with many features:
- All DeviceNet I/O modes are supported: polling, change of state, cyclic, strobed.
- unconnected Message Manager (UCMM)
- offline connection set, Device Heartbeat Messages, Device Shutdown Messages
- Auto Device Replacement (ADR)
- powerful parameter and diagnostics interfaces
- The error management for each bus user is freely configurable.
Like the FC5201 DeviceNet PCI card, the EL6752 can be used for connection to DeviceNet networks. The terminal, however, enables a more space-saving implementation since no PCI slots are required in the Industrial PC.
Product status:
regular delivery
Product information
Technical data | EL6752 | EL6752-0010 |
---|---|---|
Technology | DeviceNet master terminal | DeviceNet slave terminal |
Fieldbus | DeviceNet | |
Number of fieldbus channels | 1 | |
Data transfer rates | 125, 250, 500 kbaud | |
Interfaces | open style connector, 5-pin, according to DeviceNet specification, galvanically decoupled (Connector is supplied.) | |
Communication | DeviceNet network master (scanner) | DeviceNet slave |
Bus device | max. 63 slaves | |
Hardware diagnostics | status LEDs | |
Distributed clocks | – | |
Current consumption power contacts | – | |
Current consumption E-bus | typ. 260 mA | |
Special features | DeviceNet scanner | |
Weight | approx. 70 g | |
Operating/storage temperature | -25…+60°C/-40…+85°C | |
Relative humidity | 95%, no condensation | |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
Protect. rating/installation pos. | IP20/variable | |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc | |
Approvals/markings | CE, UL, ATEX, IECEx |
Housing data | EL-24 |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 24 mm x 100 mm x 52 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |