KL3311 | Bus Terminal, 1-channel analog input, temperature, thermocouple, 16 bit

Image similar, may contain optional accessories
KL3311 | Bus Terminal, 1-channel analog input, temperature, thermocouple, 16 bit

KL3311 | Bus Terminal, 1-channel analog input, temperature, thermocouple, 16 bit

Run LED 1
Error LED 1
+TC1
-TC1
Shield
Shield
Top view 
Contact assembly 
Observe for earthed
thermocoupler:
differential inputs
max. ± 2 V to ground
KL3311 | Bus Terminal, 1-channel analog input, temperature, thermocouple, 16 bit

KL3311 | Bus Terminal, 1-channel analog input, temperature, thermocouple, 16 bit

The KL3311 analog input terminal allows thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the 2-wire technique. Linearization over the full temperature range is realized with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3311 can also be used for mV measurement.

Product status:

regular delivery

Product information

Technical dataKL3311
Number of inputs1
Power supplyvia the K-bus
Technology2-wire
Thermocouple sensor typestypes J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Measuring rangein the range defined in each case for the sensor (default setting: type K; -100…+1370°C);
mV measurement: ±30 mV…±120 mV
Connection method2-wire
Conversion time~ 200 ms
Wiring fail indicationyes
Resolution0.1°C per digit
Measurement error/uncertainty< ±0.5% (relative to full scale value)
Electrical isolation500 V (K-bus/signal voltage)
Current consumption power contacts– (no power contacts)
Current consumption K-bustyp. 65 mA
Bit width in the process imageinput: 1 x 16 bit data (1 x 8 bit control/status optional)
Configurationno address setting, configuration via Bus Coupler or controller
Special featureselectrically isolated
Weightapprox. 70 g
Operating/storage temperature0…+55°C/-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataKL-12-8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule