The EK1122-0008 2-port EtherCAT junction can be used in an EtherCAT Terminal segment at any desired position between the EtherCAT Terminals and enables configuration of EtherCAT star topologies. A modular EtherCAT star hub can be realized by using several EK1122-0008 units in a station.
Special features:
- connection technology: 2 x M8 sockets
- connection lengths: up to 100 m
- can be used for configuring an EtherCAT star topology
The EK1122-0008 has two M8 sockets, which enable connection of an Ethernet cable with M8 connector and establish a connection to a further EtherCAT segment or to individual EtherCAT devices. The M8 sockets are compatible with the EtherCAT Box modules and therefore enables uniform cabling in the IP20 and IP67 range. The EK1122-0008 supports coupling and uncoupling of EtherCAT segments during operation (Hot Connect).
Product status:
regular delivery
Product information
Technical data | EK1122-0008 |
---|---|
Task within EtherCAT system | coupling of EtherCAT junctions |
Data transfer medium | Ethernet/EtherCAT cable (min. Cat.5), shielded |
Distance between stations | 100 m (100BASE-TX) |
Protocol | EtherCAT |
Delay | approx. 1 µs |
Data transfer rates | 100 Mbit/s |
Configuration | not required |
Bus interface | 2 x M8, shielded |
Power supply | from E-bus |
Current consumption | typ. 220 mA |
Weight | approx. 65 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
Housing data | EL-24 |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 24 mm x 100 mm x 52 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | specific push-in connection |