EL6751 | EtherCAT Terminal, 1-channel communication interface, CANopen, master/slave

Image similar, may contain optional accessories
EL6751 | EtherCAT Terminal, 1-channel communication interface, CANopen, master/slave

EL6751 | EtherCAT Terminal, 1-channel communication interface, CANopen, master/slave

Status LEDs
Fieldbus connection
Top view 
EL6751 | EtherCAT Terminal, 1-channel communication interface, CANopen, master/slave

EL6751 | EtherCAT Terminal, 1-channel communication interface, CANopen, master/slave

The Terminal enables within an EtherCAT Terminal network the integration of any CANopen devices and can either be master (EL6751) or slave (EL6751-0010). In addition, general CAN messages can be sent or received – without having to bother with CAN frames in the applications program. The terminal has a powerful protocol implementation with many features:

  • All CANopen PDO communication types are supported: event driven, time driven (using an event timer), synchronous, polling.
  • synchronization with the PC controller’s task cycle
  • SYNC cycle with quartz precision for drive synchronization, zero cumulative jitter
  • parameter communication (SDO) at start-up and when running
  • emergency message handling, guarding and heartbeat
  • powerful parameter and diagnostics interfaces
  • online bus load display

Like the FC5101 CANopen PCI card, the EL6751 can be used for connection to CANopen networks. The terminal, however, enables a more space-saving implementation since no PCI slots are required in the Industrial PC.

Product status:

regular delivery

Product information

Technical dataEL6751EL6751-0010
TechnologyCANopen master/slave terminalCANopen slave terminal
FieldbusCANopen
Number of fieldbus channels1
Data transfer rates10, 20, 50, 100, 125, 250, 500, 800, 1000 kbaud
InterfacesD-sub connector, 9-pin according to CANopen specification, galvanically decoupled
CommunicationCANopen network master and CANopen manager, optionally CANopen slave
Hardware diagnosticsstatus LEDs
Current consumption E-bustyp. 230 mA
Special featuresstatus LEDs, CANopen network master, CANopen Manager, supports RAW-CANstatus LEDs, CANopen slave
Weightapprox. 70 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataEL-24
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)24 mm x 100 mm x 52 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking
Wiringspecific push-in connection