The EL9562 power supply terminal generates two electrically isolated output voltages from the 24 V DC input voltage. The output voltages can be tapped at the terminal with a current of 0.2 A; they are electrically isolated from each other and from the input voltage. The power contacts are looped through. The power LEDs indicate the operating status of the terminal. Connecting both voltages makes it possible to create a symmetrical DC voltage.
The terminal is part of the group of supply devices with fixed voltage:
- EL9505/EL9508/EL9510/EL9512/EL9515: output voltage according to type, up to 0.5 A, without electrical isolation from the power contact supply
- EL9560: 24 V output, up to 0.1 A, with electrical isolation from the power contact supply
- EL9562/EL9562-0015: 2 x 24 V or 15 V output, up to 0.3 A, with electrical isolation from the power contact supply
- PSxxxx: DIN rail-mounted switched-mode power supply units
The terminal is part of the group of supply devices with fixed voltage:
- EL9501: operation with voltage specification of 0...20 V, up to 2 A, up to 15 W, without electrical isolation from the power contact supply
- EL9561: operation with voltage specification of 0...20 V, up to 2 A, up to 4.8 W, with electrical isolation from the power contact supply
- EL2595: operation with current specification, up to 48 V, up to 700 mA, up to 33 W
- EL2596: operation with voltage specification or current specification, up to 24 V, up to 3 A, up to 14 W
- EL4132: operation with voltage specification ±10 V, up to 20 mA (as an example from the EL41xx family)
- EL4012: operation with current specification of 0...20 mA, up to 10 V (as an example from the EL40xx family)
Product status:
regular delivery
Product information
Technical data | EL9562 |
---|---|
Technology | power supply terminal |
Short-circuit proof | yes |
Input voltage | 24 V DC (-15%/+20%) |
Output voltage | 24 V DC (-15%/+20%) |
Output current | 2 x ≤ 0,2 A |
Current consumption E-bus | 60 mA |
Insulation voltage | 1,500 V AC constant load field side/E-bus |
Insulation voltage input/output | 500 V AC permanent load (field side) |
Special features | automatic restart after short circuit, diagnostics UIN/UOUT |
Weight | approx. 55 g |
Operating temperature | 0…55°C |
Storage temperature | -25…+85°C |
Relative humidity | 95%, no condensation |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule