The ELM3002-0405 EtherCAT Terminal combines the high-voltage measurement of the ELM3002-0205 and the low-voltage measurement of the ELM3002-0305 in a 2-channel terminal. This means that an EtherCAT Terminal can simultaneously measure the total voltage of a cell stack or generator, as well as its current via a shunt. The synchronous coupling of several terminals – for the purpose of measuring a 3-phase system, for example – is possible using distributed clocks.
The measuring range is selected in the CoE, as are the other setting options such as the filter parameters. Regardless of the signal configuration, all ELM modules have the same technological properties, and the ELM3002-0405 with oversampling offers a maximum sampling rate of 50,000 samples per second and channel. The terminal is equipped with 4 mm laboratory sockets.
This terminal is also available as a variant with an individual calibration certificate. (See related products)
Extensive documentation is available from Beckhoff sales, support or measurement@beckhoff.com.
This ELM3xxx series measurement terminal enables efficient implementation of complex system-integrated data acquisition systems (DAQ) that place high demands on measurement accuracy and time synchronization.
Product status:
product announcement
Product information
System data | ELM300x |
---|---|
Voltage measurement | Kanal 1: ±1200/600/360/60 V
Kanal 2: ±5/2.5/1/250/150/100/60 mV |
Technical data | ELM3002-0405 |
---|---|
Number of channels | 2 |
Technology | voltage measurement |
Signal type | differential |
Connection technology | 2-wire |
Connection type | 4 mm laboratory plug, service plug 1-pin |
Max. sampling rate | max. 20 µs/50 ksps (per channel, simultaneously) |
Oversampling factor | n = 1…100 selectable |
Internal resistance | typ. > 10 MΩ |
Measurement error/uncertainty | typ. < ±200 ppm/±0.02% in some measuring ranges, relative to the respective full scale value (DC), see documentation |
Temperature coefficient | up to typ. < 50 ppm/K in some measuring ranges, see documentation |
Functional diagnostics | yes |
Distributed clocks | yes, accuracy << 1 µs |
Resolution | 24 bit (incl. sign) |
Measurement class/overvoltage class | 1000 V CAT II, 1000 V CAT III (in preparation), 600 V CAT IV (in preparation); according to EN61010-2-030 |
Electrical isolation channel/channel | reinforced insulation, test voltage 6 kV DC, production test |
Electrical isolation channel/bus | reinforced insulation, test voltage 6 kV DC, production test |
Electrical isolation channel/SGND | reinforced insulation, test voltage 6 kV DC, production test |
Current consumption E-bus | typ. 460 mA |
Weight | approx. 350 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Thermal dissipation | typ. 3 W |
Special features | ExtendedRange 107%, free numeric filter, TrueRMS, integrator/differentiator, non-linear scaling, PeakHold |
Approvals/markings | CE |
Housing data | ELM-30-xpin |
---|---|
Design form | metal housing with signal LEDs |
Material | zinc die-cast |
Dimensions (W x H x D) | 30 mm x 100 mm x 95 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.2…1.5 mm², st*: 0.2…1.5 mm², f*: 0.25…0.75 mm² |
Connection cross-section AWG | s*: AWG24…14, st*: AWG24…14, f*: AWG24…14 |
Stripping length | 8…9 mm |
*s: solid wire; st: stranded wire; f: with ferrule