DetachFixClose

Headquarters Malaysia
Beckhoff Automation Sdn. Bhd.

Lot 7, Lorong Teknologi A, Jalan Teknologi,
Taman Perindustrian Sains Selangor, Kota Damansara,
47810, Petaling Jaya, Selangor, Malaysia

+60 3 6151-3088
info@beckhoff.com.my
www.beckhoff.com/ms-my/

EL2489 | EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, ground switchingNew

Image similar, may contain optional accessories
EL2489 | EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, ground switching

EL2489 | EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, ground switching

Signal LEDs
1…8
Signal LEDs
9…16
Power contact
+24 V
Power contact 0 V
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Top view 
Contact assembly 
EL2489 | EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, ground switching

EL2489 | EtherCAT Terminal, 16-channel digital output, 24 V DC, 0.5 A, ground switching

The EL2489 digital output terminal connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. The EtherCAT Terminal has 16 channels, whose signal states are indicated by LEDs. The connection technology is particularly suitable for single-ended inputs. All components have to use the same reference point as the EL2489. The power contacts are connected through. In the EL2489 the outputs are supplied via the 0 V DC power contact.

 

Special features:

  • ground switching
  • connection of different load types possible (ohmic, inductive, lamp load)
  • max. output current 0.5 A per channel
  • overload and short-circuit proof outputs and reverse polarity protection
  • tool-free connection by direct plug-in technology for solid wire conductors
  • space-saving use in the control cabinet
  • direct connection of multi-channel actuators in 1-wire connection technology in the smallest space
  • increased packing density with 16 connection points in the housing of a 12 mm terminal block

Product status:

product announcement | estimated market release 1st quarter 2025

Product information

Technical dataEL2489
Connection technology1-wire
Specificationground switching
Number of outputs16
Nominal voltage24 V DC (-15%/+20%)
Load typeohmic, inductive, lamp load
Distributed clocks
Max. output current0.5 A (short-circuit proof) per channel
Reverse voltage protectionyes
Electrical isolation500 V (E-bus/field potential)
Weightapprox. 70 g
Operating/storage temperature0…+55°C/-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE
Housing dataEL-12-16pin
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWGs*: AWG28…16,
st*: AWG22…16,
f*: AWG26…19
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule