분리고정닫기

본사 대한민국
Beckhoff Automation Co., Ltd.

대륭테크노타운 3차 12층
가산디지털2로 115
08505 금천구, 서울특별시, 대한민국

+82 2 2107-3242
info-kr@beckhoff.com
www.beckhoff.com/ko-kr/

EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 kspsNew

Image similar, may contain optional accessories
EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

Run LED
Err LED
CH1...8
Power contact
+24 V
Power contact 0 V
Ch1 Output
Ch2 Output
Ch3 Output
Ch4 Output
Ch5 Output
Ch6 Output
Ch7 Output
Ch8 Output
GND
GND
GND
GND
GND
GND
GND
GND
Top view 
Contact assembly 
Image similar, may contain optional accessories
EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

EL307x, EL4x7x: The new generation of multi-functional analog terminals

EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

EL4078 | EtherCAT Terminal, 8-channel analog output, multi-function, ±10 V, ±20 mA, 16 bit, 2 ksps

EL307x, EL4x7x: The new generation of multi-functional analog terminals

A new generation of Beckhoff analog I/Os

A new generation of Beckhoff analog I/Os

The EL4072, EL4074, and EL4078 analog output terminals output 10 V/20 mA standard signals with 16-bit resolution and up to 2000 values per second. Each channel can be parameterized individually via the controller/TwinCAT. All known standard signals in the range of ±10 V and ±20 mA can be output per channel – for example, 4…20 mA. The current outputs can also drive high burden resistors and report an overload or wire break or, in the case of a voltage output, a short circuit. The voltage and current outputs are designed as single-ended, which means that one connection point of each channel is already connected in the terminal to +24 V or GND and no longer needs to be wired separately. The EL4072 and EL4074 have 24 V/0 V contacts for the supply of the actuators. With a technical output range of ±107% of the nominal range, the channels can even transport unconventional setpoints, such as for error reporting purposes.

Product status:

product announcement | estimated market release 4th quarter 2024

Product information

Technical dataAnalog output
Number of outputs8
Wiring2-wire
Ground reference (input)single-ended
Max. sampling ratemin. 500 µs (max. 2 ksps) per channel
Sampling typemultiplex
Loadvoltage: > 5 kΩ (short-circuit-proof)
current: < 300 Ω
Output range, nominal-10/0…+10 V | -20/0/+4…+20 mA
Output range, technical-10.73…+10.73 V | -21.47…+21.47 mA
Resolution16 bit (incl. sign)
Measurement error/uncertaintytyp. < ±0.07%AEW (voltage and current, at 25°C ±5°C, otherwise < ±0.1%)
Electrical isolation channel/channelno
Technical dataGeneral
Power supplyvia power contacts, 24 V DC (-15 %/+20 %)
Electrical isolationchannel/E-bus: functional separation 707 V DC type test
Current consumption power contactstyp. 60 mA (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads)
Current consumption E-bustyp. 90 mA
Distributed clocks
Special featuresU/I parameterizable, ExtendedRange 107 %, output diagnosis
Weightapprox. 65 g
Operating/storage temperature0…+55°C/-25…+85°C
Relative humidity95%, no condensation
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE
Housing dataEL-12-16pin
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWGs*: AWG28…16,
st*: AWG22…16,
f*: AWG26…19
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use