The EL3444 EtherCAT Terminal enables the measurement of all relevant electrical data of the supply network and carries out simple pre-evaluation. Since the EL3444 itself has no voltage inputs, the voltage measured values are transmitted via EtherCAT by an EL3453 to be installed once per network. The current of up to six galvanically isolated phases is fed in directly. All measured currents and voltages are available as root-mean-square values. In the EL3444 terminal, the effective power and energy consumption for each phase are calculated. The RMS values of voltage U and current I as well as the active power P, apparent power S, reactive power Q, frequency f, phase shift angle cos φ and harmonic are available. The EL3444 offers extended functionality for mains analysis and energy management.
Product status:
product announcement | estimated market release 4th quarter 2024
Product information
Technical data | EL3444 |
---|---|
Number of inputs | 4 x current |
Oversampling factor | – |
Distributed clocks | optional (necessary for distributed power measurement) |
Update interval | 100 ms |
Measured values | current (and with the EL3453: voltage, effective, reactive and apparent power, active, reactive and apparent energy, cos φ, frequency, THD, harmonic (up to 63rd harmonic)) |
Measuring voltage | – |
Measuring current | 10 A (AC/DC), potential-free |
Measurement error/uncertainty | 1% relative to full scale value (I), 1.25% calculated value, see documentation |
Update time | net-synchronous |
Monitoring function | undercurrents/overcurrents (adjustable) |
Electrical isolation | 4500 V |
Current consumption power contacts | – |
Current consumption E-bus | typ. 120 mA |
Special features | In combination with an EL3453, the EL3444 allows the measurement of real power values (for apparent, reactive and active power) via distributed power measurement. |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Weight | approx. 75 g |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Loading content ...
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2024 - Terms of Use