LeválasztásHozzáadásBezárás

Magyarországi központ
Beckhoff Automation Kft.

Magyarország, 1097 Budapest
Táblás utca 36–38. G. ép.

+36 1 50199-40
info@beckhoff.hu
www.beckhoff.com/hu-hu/

EPP9022-9060 | EtherCAT P Box, with voltage diagnostics, TwinSAFE SC

Image similar, may contain optional accessories
EPP9022-9060 | EtherCAT P Box, with voltage diagnostics, TwinSAFE SC

EPP9022-9060 | EtherCAT P Box, with voltage diagnostics, TwinSAFE SC

EtherCAT P signal input
EtherCAT P signal output
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply downstream
connection
1 | Tx+/GNDS
2 | Rx+/GNDP
3 | Rx-/UP
4 | Tx-/US
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
Top view 
Connector assignment 
EPP9022-9060 | EtherCAT P Box, with voltage diagnostics, TwinSAFE SC

EPP9022-9060 | EtherCAT P Box, with voltage diagnostics, TwinSAFE SC

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

Hannover Messe 2019

EtherCAT P: The one cable solution – One step closer to automation without control cabinets

Hannover Messe 2019

The EPP9022-9060 EtherCAT P Box in space-saving form factor can be used for diagnosing and measuring the voltages US and UP and currents IS and IP, both temporarily during commissioning and permanently during operation. Even without an EtherCAT master, the voltage range is displayed on the box by LEDs (green, yellow and red). In a running EtherCAT network, the values of US, UP, IS and IP can also be read out as process data in the master. The voltage levels for the LED displays can be adjusted by CoE. In addition the EPP9022-9060 is equipped with an M8 power socket to which an external multimeter can be connected for measuring the voltages.

With the aid of the TwinSAFE SC technology (TwinSAFE Single Channel) it is possible to make use of standard signals for safety tasks in any network or fieldbus. The properties typical for the signals and the standard functions of the I/O components are retained. The data from the TwinSAFE SC components is fed via a TwinSAFE protocol to the TwinSAFE Logic, where it can be used in the context of safety-relevant applications. Detailed examples confirmed/calculated by the TÜV SÜD for the correct application of the TwinSAFE SC components and the respective normative classifications can be found in the TwinSAFE application manual.

Product status:

regular delivery

Product information

Technical dataEPP9022-9060
ProtocolEtherCAT P
Bus interfaceM8 socket, P-coded, shielded
Task within EtherCAT systemdiagnostics of the US/UP voltages and IS/IP currents
Number of channelsIN: 1 x EtherCAT P, OUT: 1 x EtherCAT P
Nominal voltage24 V DC (-15%/+20%)
Total currentfeed-in max. 3 A per US and UP
Current consumption from UStyp. 100 mA
Current rating per portmax. 3 A per US and UP
Special featuresdiagnostic LED for US, diagnostic LED for UP, TwinSAFE SC
Weightapprox. 90 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing dataEPPxxxx-006x
Dimensions (W x H x D)30 mm x 86 mm x 22 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3

Loading content ...

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use