The KL3362 analog input terminal makes it possible to perform non-central preliminary processing of analog values. The input values are digitized with a 14 bit resolution and written into an internal memory. An efficient processor can pre-process the values. Limit values and maximum and minimum values can be determined or monitored. The KL3362 can also carry out envelope curve monitoring. A trigger starts the cyclical processes. The result or all the measured values are transported to the higher-level automation unit.
Product status:
regular delivery
Product information
Technical data | KL3362 |
---|---|
Number of inputs | 2 analog, 1 trigger |
Power supply | via the K-bus |
Signal voltage | -10…+10 V |
Technology | high-speed data logger |
Internal resistance | > 500 kΩ |
Internal resistance E1-GND, E2-GND | > 500 kΩ |
Supply voltage | – |
Conversion time | < 100 µs, configurable (10 µs with fast sampling mode) |
Resolution | 14 bit + sign |
Measurement error/uncertainty | < ±0.5% (relative to full scale value) |
Internal memory | 32 kbytes |
Trigger | configurable |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 120 mA |
Bit width in the process image | input/output: 2 x 16 bit data (2 x 8 bit control/status per channel) |
Special features | high-speed analog analysis |
Weight | approx. 55 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL, ATEX, IECEx |
Pluggable wiring | for all KSxxxx Bus Terminals |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | KL-12-8pin | KS-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Ordering information | |
---|---|
KL3362 | Bus Terminal, 2-channel analog input, voltage, ±10 V, 15 bit, oscilloscope function |
KS3362 | Bus Terminal, 2-channel analog input, voltage, ±10 V, 15 bit, oscilloscope function , pluggable wiring |