The BK5220 Economy plus Bus Coupler connects the DeviceNet bus system to the electronic terminal blocks, which can be extended in modular fashion. One unit consists of one Bus Coupler, any number of up to 64 terminals and one end terminal. With the K-bus extension technology, the BK5220 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The Economy plus series supports all Beckhoff system Bus Terminals and it can process in its full configuration 1020 digital signals and a maximum of 256 analog input and output channels per slave.
The Bus Coupler operates on the basis of the CAN protocol. The DeviceNet standard on which the Bus Coupler is based allows the operation of diverse DeviceNet devices in one network. DeviceNet is based on a definition of communication objects for the exchange of data from the sensor/actuator area that is especially oriented to automation technology.
The Bus Coupler and Bus Terminals can be parameterized on a PC using the KS2000 configuration set. Commissioning is also possible without the KS2000. Corresponding EDS data files are available for DeviceNet configuration tools.
Product status:
regular delivery
Product information
Technical data | BK5220 |
---|---|
Number of Bus Terminals | 64 (255 with K-bus extension) |
Max. number of bytes fieldbus | 512 byte input and 512 byte output |
Digital peripheral signals | 1,020 inputs/outputs |
Analog peripheral signals | 256 inputs/outputs |
Configuration possibility | via KS2000 or the controller |
Data transfer rates | automatic detection |
Bus interface | 1 x open pluggable connector, 5-pin, included |
Data transfer medium | screened, twisted copper wire with power supply, 5-pin |
Power supply | 24 V DC (-15%/+20%), through bus cable 11…25 V (conforms to DeviceNet specification) |
Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
Starting current | approx. 2.5 x continuous current |
Recommended fuse | ≤ 10 A |
Current supply K-bus | 1750 mA |
Power contacts | max. 24 V DC/max. 10 A |
Electrical isolation | 500 V (power contact/supply voltage Bus Coupler) |
Operating modes | bit strobe, polling, cyclic, change of state (COS) |
DeviceNet type | communications adapter |
Weight | approx. 130 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | BKxxxx, BCxxxx |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 51 mm x 100 mm x 69 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule