The PS9421-4840-0000 redundancy module is suitable for the setup of a redundant, fail-safe supply network. It is equipped with two inputs, to which two 2 x 20 A power supplies with 24 V DC or 48 V DC can be connected. The output can continuously conduct rated currents of up to 40 A. The redundancy module uses MOSFETs to decouple the two inputs; this reduces heat generation and the voltage drop between input and output. The redundancy module requires no additional auxiliary voltage and is autonomous even in case of a short-circuit at the output. Due to the low losses, the module is very compact and requires an installation width of just 32 mm on the DIN rail.
Product status:
regular delivery
Product information
Technical data | PS9421-4840-0000 |
---|---|
Input voltage | DC 24…56 V |
Input current | 2 x 20 A |
Input current for 5 s | 2 x 20…32.5 A |
Output current | 0…40 A |
Output current 5 s | 40…65 A |
Voltage drop input/output | typ. 60 mV; input 2 x 10 A, typ. 120 mV; input 2 x 20 A |
Power loss | typ. 1.8 W; 48 V input: 2 x 10 A, typ. 2.3 W; 48 V input: 1 x 20 A |
Operating temperature | -40…+70 °C |
Shock resistance | conforms to EN 60068-2-27 |
Vibration resistance | conforms to EN 60068-2-6 |
Weight | approx. 360 g |
Approvals/markings | CE, UL508, ATEX, IECEx, Class I Div2 |
Protection rating | IP20 |
Housing data | Power supply |
---|---|
Dimensions (W x H x D) | 46 mm x 124 mm x 127 m |
Material | aluminum |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Wiring | input/output: screw type connection |
Connection cross-section | input/output: e*: 0.5…16 mm², f*: 0.5…10 mm², a*: 0.5…10 mm² |
Connection cross-section AWG | Input/Output: AWG 22-8 |
Stripping length | 12 mm |
*s: solid wire; st: stranded wire; f: with ferrule