SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

EL1429 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, positive/ground switchingNew

Image similar, may contain optional accessories
EL1429 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, positive/ground switching

EL1429 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, positive/ground switching

Signal LEDs
1…8
Signal LEDs
9…16
Power contact
+24 V
Power contact 0 V
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
Top view 
Contact assembly 
EL1429 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, positive/ground switching

EL1429 | EtherCAT Terminal, 16-channel digital input, 24 V DC, 3 ms, positive/ground switching

EtherCAT digital terminals: Tried-and-tested features for maximum flexibility

EtherCAT digital terminals: Tried-and-tested features for maximum flexibility

The EL1429 digital input terminal acquires the binary 24 V control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The EtherCAT Terminal has 16 channels, whose signal states are indicated by LEDs.

 

Special features:

  • flexible switching logic: positive or ground switching, per channel
  • no bouncing due to mechanical switches thanks to 3 ms input filter
  • tool-free connection by direct plug-in technique for solid wire conductors
  • space-saving use in the control cabinet
  • direct connection of multi-channel sensors in 1-wire connection technology in the smallest space

Product status:

product announcement

Product information

Technical dataEL1429
Connection technology1-wire
Specificationpositive/ground switching
Number of inputs16
Nominal voltage24 V DC (-15%/+20%)
“0” signal voltage9…15 V at 24 V DC nominal voltage
“1” signal voltage0…5 V and 19…24 V at 24 V DC nominal voltage
Input currenttyp. 2.5 mA at 24 V nominal voltage
Input filtertyp. 3.0 ms
Distributed clocks
Current consumption power contactstyp. 2 mA + load
Current consumption E-bustyp. 110 mA
Electrical isolation500 V (E-bus/field potential)
Weightapprox. 65 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL
Housing dataEL-12-16pin
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWGs*: AWG28…16,
st*: AWG22…16,
f*: AWG26…19
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use