SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

KL3214 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit, 3-wire connection

Image similar, may contain optional accessories
KL3214 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit, 3-wire connection

KL3214 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit, 3-wire connection

Run LED
Err LED
CH1...4
Power contact
+24 V
Power contact 0 V
+R1
RL1
+R2
RL2
+R3
RL3
+R4
RL4
-R1
-R2
-R3
-R4
Top view 
Contact assembly 
KL3214 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit, 3-wire connection

KL3214 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit, 3-wire connection

The KL3214 analog input terminal allows four resistance sensors to be connected directly. The Bus Terminal circuit can operate sensors using the 3-wire technique in a compact 12 mm housing. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The Bus Terminal’s standard settings are: resolution 0.1°C. Sensor malfunctions such as broken wires are indicated by error LEDs.

Product status:

regular delivery

Product information

Technical dataKL3214
Number of inputs4
Power supplyvia the K-bus
Input filter limit frequencytyp. 1 kHz
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, potentiometer: 10 Ω…1.2/4 kΩ, KTY sensors (types see documentation)
Measuring range-200…+850°C (Pt sensors); -60…+250°C (Ni sensors)
Connection method3-wire
Conversion timeapprox. 170 ms default setting
Measuring current< 0.5 mA (load-dependent)
Resolution0.1°C per digit
Measurement error/uncertainty< ±0.5°C for Pt sensors
Electrical isolation500 V (K-bus/signal voltage)
Current consumption power contacts
Current consumption K-bustyp. 120 mA
Special featuresopen-circuit recognition
Weightapprox. 60 g
Operating/storage temperature0…+55°C/-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL
Housing dataHD housing
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Stripping length8…9 mm

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use