SoltarAdjuntarCerrar

Oficina central México
Beckhoff Automation, S.A. de C.V.

Boulevard Manuel Ávila Camacho 2610, Torre B, Piso 9, Colonia Valle de los Pinos, Tlalnepantla de Baz
Estado de México CP 54040, México

+52 55 75998058
mexico@beckhoff.com
www.beckhoff.com/es-mx/

KL3208-0010 | Bus Terminal, 8-channel analog input, temperature, RTD (Pt1000, NTC), 16 bit

Image similar, may contain optional accessories
KL3208-0010 | Bus Terminal, 8-channel analog input, temperature, RTD (Pt1000, NTC), 16 bit

KL3208-0010 | Bus Terminal, 8-channel analog input, temperature, RTD (Pt1000, NTC), 16 bit

Signal LEDs
1…8
Error LEDs
9...16
Power contact
+24 V
Power contact 0 V
+R1
+R2
+R3
+R4
+R5
+R6
+R7
+R8
-R1
-R2
-R3
-R4
-R5
-R6
-R7
-R8
Top view 
Contact assembly 
KL3208-0010 | Bus Terminal, 8-channel analog input, temperature, RTD (Pt1000, NTC), 16 bit

KL3208-0010 | Bus Terminal, 8-channel analog input, temperature, RTD (Pt1000, NTC), 16 bit

The KL3208-0010 analog input terminal enables connection of eight resistance sensors. The Bus Terminal’s circuitry can handle sensors using the 2-wire technique. Linearization over the full temperature range is realized with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminal’s standard settings are: resolution 0.01°C within the temperature range of Pt/Ni1000 sensors. The error LEDs indicate sensor faults (e.g. a broken wire).

The HD Bus Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm terminal block.

Product status:

regular delivery

Product information

Technical dataKL3208-0010
Number of inputs8
Power supplyvia the K-bus
Technology2-wire
Sensor typesPt1000 (default), Ni1000, resistor/potentiometer 6/65/655 kΩ, NTC 1.8 k/2.2 k/3 k/5 k/10 k/20 k/100 k
Measuring range-50…+150°C (depending on sensor type)
Connection method2-wire
Conversion time~ 1 s
Measuring currenttyp. < 0.5 mA
Resolution0.01°C per digit
Measurement error/uncertainty-20…+60°C: ±0.25°C at 25°C ambient temperature; -50…+150°C: ±1.5°C (for Pt/Ni sensors)
Electrical isolation500 V (K-bus/signal voltage)
Current consumption power contacts
Current consumption K-bustyp. 85 mA
Bit width in the process imageinput: 8 x 16 bit data (8 x 8 bit control/status optional)
Configurationno address setting, configuration via Bus Coupler or controller
Special featuresopen-circuit recognition, cable resistance calibration, particularly suitable for building automation
Weightapprox. 75 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataHD housing
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Stripping length8…9 mm

*s: solid wire; st: stranded wire; f: with ferrule

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use