The EPI2008-0001 IO-Link box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A, and although the total current is limited to 4 A, they indicate their status through light emitting diodes. The signals are connected via M8 screw type connectors. The outputs are short-circuit proof and protected against inverse connection.
Product status:
regular delivery
Product information
Technical data | EPI2008-0001 |
---|---|
Communication | IO-Link |
Interfaces | 1 x M12 plug, A-coded |
Data transfer rates | 230.4 kbaud (COM 3) |
Specification version | IO-Link V1.1, Class B |
Number of outputs | 8 |
Output connections | M8, screw type |
Load type | ohmic, inductive, lamp load |
Nominal output voltage | 24 V DC (-15%/+20%) |
Max. output current | 0.5 A per channel, from P24, individually short-circuit proof |
Short-circuit current | typ. 1.5 A |
Current consumption | typ. 100 mA from L+ |
Auxiliary power current | typ. 20 mA + load |
Electrical isolation | L+/P24: yes |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |
Housing data | 8 x M8, 4 x M12 |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |