The EL2722 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two mutually locked outputs, whose signal state is indicated by LEDs.
Special features:
- Triac output
- 2 x make contacts with mutual interlocking
- Connection of ohmic and inductive loads from 12 to 230 V AC
- Suitable for conventional blind motors
Product status:
regular delivery
Product information
Technical data | EL2722 |
---|---|
Connection technology | triac output, 2-wire |
Number of outputs | 2 x make contacts, mutually locked |
Rated load voltage | 12…230 V AC |
Load type | ohmic, inductive |
Distributed clocks | – |
Max. output current | 1 A (leakage current: typ. 0.8 mA, max. 1.5 mA) per channel |
Switching times | in zero crossing, 0.1…10 ms |
Rotating field frequency | 47…63 Hz |
Surge voltage protection | > 275 V |
Peak current | 40 A (16 ms), 1.5 A (30 s) |
Standby current | 0.6 mA |
Leakage current (OFF state) | typ. 0.8 mA, max. 1.5 mA |
Switch-on time | 0.1…10 ms, zero crossing |
Switch-off time | T/2 |
Residual voltage | max. 1.5 V (60 mA…1 A), 150 Ω (< 60 mA) |
Current consumption E-bus | typ. 120 mA |
Electrical isolation | 500 V (E-bus/field voltage), 3750 V AC (1 min.) |
Current consumption power contacts | – |
Bit width in the process image | 2 outputs |
Configuration | no address or configuration setting |
Special features | suitable for conventional blind motors |
Weight | approx. 55 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE |
Housing data | EL-12-8pin | ES-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Ordering information | |
---|---|
EL2722 | EtherCAT Terminal, 2-channel triac output, 12…230 V AC, 1 A |
ES2722 | EtherCAT Terminal, 2-channel triac output, 12…230 V AC, 1 A, pluggable wiring |
Loading content ...
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2024 - Terms of Use