The EJ3214 EtherCAT plug-in module allows four resistance sensors to be connected directly. The module's circuit can operate sensors using the 2- or 3-wire technique. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The EJ3214’s standard settings are: resolution 0.1°C. The signal state is indicated by light emitting diodes. Sensor malfunctions such as broken wires are indicated by error LEDs.
Product status:
regular delivery
Product information
Technical data | EJ3214 |
---|---|
Connection method | 2- or 3-wire (default: 3-wire) |
Number of inputs | 4 |
Measuring range | -200…+850°C (Pt sensors); -60…+250°C (Ni sensors) |
Technology | temperature measurement (RTD) |
Distributed clocks | – |
Input filter limit frequency | typ. 1 kHz |
Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
Conversion time | approx. 170 ms default setting |
Resolution | 0.1°C per digit |
Measurement error/uncertainty | < ±0.5°C for Pt sensors, 4 x 3-wire connection |
Electrical isolation | 500 V (E-bus/field potential) |
Current consumption E-bus | typ. 160 mA |
Special features | integrated digital filter, limit value monitoring, variable connection technology |
Weight | approx. 30 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Relative humidity | 95%, no condensation |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Protect. rating/installation pos. | IP20/see documentation |
Approvals/markings | CE, UL |
Housing data | EJ-12-16pin |
---|---|
Design form | EtherCAT I/O plug-in module |
Material | polycarbonate |
Installation | on signal distribution board |
Mechanical coding | EJ plug-in module: signal-specific coding pins on the housing, signal distribution board: holes in the printed circuit board |
Locking | latching lug in circuit board cut-out |
Connection method | field wiring: application-specific wiring level on the signal distribution board,
EJ plug-in module: 2 x 20-pin socket strip |
Dimensions (W x H x D) | 12 mm x 66 mm x 55 mm |