The EPX1058-0022 EtherCAT Box acquires signals from NAMUR field devices according to IEC 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
By software, it is possible to select channel by channel whether a positive switching or negative switching sensor is to be connected. Thus, no changes to the PLC are required for the connection of both NAMUR break contacts or make contacts. The red error LEDs can be switched off, which allows the connection of dry contacts without signaling an error.
Product status:
regular delivery
Product information
Technical data | EPX1058-0022 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
Specification | NAMUR (IEC 60947-5-6) |
Number of inputs | 8 |
Input connections | M12 x 1, 5-pin, a-coded |
Connection method | 2-wire |
Open circuit voltage | typ. 8.2 V DC |
“0” signal current | ≤ 1.2 mA |
“1” signal current | ≥ 2.1 mA |
Switching hysteresis | typ. 300 µA |
Short-circuit current | typ. 7 mA |
Fault detection | I ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit) |
Max. switching frequency | 1 kHz |
Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
Sensor supply | from load supply voltage UP |
Current consumption from US | 50 mA |
Special features | can be parameterized by channel: NAMUR NO/NC, potential-free contacts NO/NC |
Weight | approx. 250 g |
Operating/storage temperature | -25…+70°C/-40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings | CE, UL, ATEX, IECEx |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Ex marking | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II 3(1)D Ex tc [ia Da] IIIC T135 °C Dc I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc Ex tc [ia Da] IIIC T135 °C Dc [Ex ia Ma] I |
Housing data | 16 x M8, 8 x M12 |
---|---|
Dimensions (W x H x D) | 60 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4 |
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2024 - Terms of Use