The EL3314-0002 analog input terminal allows the direct 2-wire connection of four thermocouples. The channels are electrically isolated from one another and from the E-bus, thus preventing interference and damage due to cross-currents. Various types of thermocouple are supported; the voltage is calculated in temperature directly in the terminal. The terminal can also be used for mV measurements. A broken wire is signaled by the error LEDs and on the fieldbus. Cold junction compensation takes place by means of precise internal temperature measurement at the connecting terminals, but operation with an external cold junction is also possible.
Product status:
regular delivery
Product information
Technical data | EL3314-0002 |
---|---|
Number of inputs | 4 |
Power supply | via the E-bus |
Distributed clocks | – |
Input filter limit frequency | typ. 1 kHz |
Connection method | 2-wire |
Conversion time | approx. 1.6 s up to 5 ms, depending on configuration and filter setting, default: approx. 110 ms |
Voltage measurement | ±78 mV, ±2,5 V |
Resolution | 24 bit, presentation adjustable: 0.1/0.01/0.001°C or 1 µV per digit |
Temperature measurement (thermocouple) | type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) |
Measurement uncertainty (temperature measurement) | at 23°C ambient temperature, with internal cold junction, according type: B: ±2.2°C; C: ±2.4°C; E: ±1.8°C; J: ±1.9°C; K: ±1.9°C; L: ±1.8°C; N: ±1.9°C; R: ±2.1°C; S: ±2.1°C; T: ±1.8°C; U: ±1.8°C; for further details see documentation |
Measurement uncertainty (voltage measurement) | at ±78 mV, 23°C ambient temperature: < ±0.06% (relative to full scale value) |
Electrical isolation | 2500 V functional isolation (test voltage channel/channel and channel/fieldbus, production test) |
Current consumption power contacts | – |
Current consumption E-bus | typ. 200 mA |
Special features | channel by channel wire break detection, internal and external cold junction, firmware filter adjustable, simultaneous measurement of the channels |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Weight | approx. 60 g |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings | CE |
Protect. rating/installation pos. | IP20/variable |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule