LossaFästStäng

EP6001-0002 | EtherCAT Box, 1-channel communication interface, serial, RS232/RS422/RS485, M12

Image similar, may contain optional accessories
EP6001-0002 | EtherCAT Box, 1-channel communication interface, serial, RS232/RS422/RS485, M12

EP6001-0002 | EtherCAT Box, 1-channel communication interface, serial, RS232/RS422/RS485, M12

EtherCAT signal input
EtherCAT signal output
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
RS232
1 | Vcc
2 | Tx
3 | GNDS
4 | Rx
5 | Shield
RS485/RS422TX
1 | Tx-
2 | Tx+
3 | GNDS
4 | Vcc
5 | Shield
RS422RX
1 | Rx-
2 | Rx+
3 | GNDS
4 | Vcc
5 | Shield
DIO
1 | +24 V DC US
2 | In-/Output B
3 | GNDS
4 | In-/Output A
5 | reserved
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
Top view 
Connector assignment 
Channel 1, RS232 
Channel 1, RS485/RS422TX 
Channel 1, RS422RX 
Channel 1, DIO 
EP6001-0002 | EtherCAT Box, 1-channel communication interface, serial, RS232/RS422/RS485, M12

EP6001-0002 | EtherCAT Box, 1-channel communication interface, serial, RS232/RS422/RS485, M12

The EP6001-0002 serial interface module allows the connection of devices with an RS232 or RS422/RS485 interface. The module transmits the data in a fully transparent manner to the higher-level automation device. The active serial communication channel functions independently of the higher-level bus system in full duplex mode at up to 115,200 baud, while a 864 byte receive buffer and a 128 byte send buffer are available. The 1-channel version has an increased end device power supply of up to 1 A, the connector assignment depends on the selected interface. The two integrated digital inputs/outputs allow the connection of additional sensors/actuators in order, for example, to trigger the reading process of the barcode reader or, depending on the result, to initiate an action. In conjunction with the TwinCAT Virtual Serial COM Driver the EP6001-0002 can be used as a normal Windows COM interface.

Product status:

regular delivery

Product information

Technical dataEP6001-0002
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
Data transfer channels1
Interfacesindividually selectable from RS232, RS485, RS422
Data transfer rates300…115,200 baud; 9600 baud (8 bit, no parity, 1 stop bit) is preset
Communication TxD and RxD, full duplex
Bit distortion< 3%
Cable lengthRS232: max. 15 m; RS422/RS485: approx. 1000 m
Data buffer864 bytes receive buffer, 128 bytes transmit buffer
Sensor supply+5 V DC, 1 A
Connection methodM12 socket, 5-pin, a-coded
Number of channels2 digital inputs or outputs
Input filter10 µs (for digital inputs)
“0” signal voltage-3…+5 V
“1” signal voltage11…30 V
Input currenttyp. 3 mA (EN 61131-2, type 3)
Load typeohmic, inductive, lamp load
Rated load voltage24 V DC (-15%/+20%)
Max. output current0.5 A per channel, individually short-circuit proof
Short-circuit currenttyp. 1.5 A
Nominal voltage24 V DC (-15%/+20%)
Distributed clocks
Current consumption from UStyp. 130 mA + sensor supply
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation500 V
Special featureseasy integration of serial end devices
Weightapprox. 165 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing data8 x M8, 4 x M12
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3