OdpniPripniZapri

EPP3754-0702 | EtherCAT P Box, 4-channel analog input, ID switch, multi-function, M12New

The EPP3754-0702 EtherCAT P Box has four analog multi-functional inputs, which can be parameterized individually and extensively:

 

  • voltage measurement: ±5 mV to ±30 V (incl. ±10 V), 0...10 V, 0...5 V
  • current measurement: ±20 mA, 4...20 mA, 0...20 mA
  • resistance measurement: 0...5 kΩ
  • electrical resistance R in 2-/3-/4-wire connection
  •  RTD measurement in 2-/3-/4-wire connection
  • potentiometer: min. 1 kΩ

 

The measured values are digitized with a 16-bit resolution and transmitted electrically isolated to the higher-level automation device. The input filters and their associated conversion times are configurable in a wide range. The inputs can, if required, be scaled differently, and automatic limit value monitoring is also available. EtherCAT is used for parameterization purposes. The parameters are stored in the module.

 

The EPP3754-0702 has three additional hexadecimal ID switches. In this way, an individual address from 0...4095 can be set, allowing unique identification regardless of installation position, as required by some device profiles for certain industries, such as the semiconductor industry.

Product status:

product announcement | estimated market release 2nd quarter 2025

Product information

Technical dataAnalog input
Conversion time~ 100 µs
Resolution16 bit (incl. sign)
Sensor typesanalog sensors, thermocouple: type B, C, E, J, K, L, N, R, S, T, U, mV measurement,
temperature: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000,
resistance measurement (e.g. potentiometer, 10 Ω…1.2/4 kΩ)
Signal type-10/0...+10 V | -20mA/0/4...20 mA, RTD/Pt100/Pt1000, ±30/±60/±75 mV (thermocouple), parameterizable per channel
Common-mode voltage UCMmax. 35 V
Internal resistance> 200 kΩ | typ. 85 Ω + diode voltage
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filter limit frequency5 kHz
Input filterconfigurable
Sensor supplyfrom load supply voltage, max. 0.5 A, short-circuit proof in total
Technical dataGeneral
ProtocolEtherCAT
Bus interface2 x M8 socket, P-coded, shielded
Number of configurable IDs4096
Number of inputs4
Input connectionsM12 x 1, 5-pin, a-coded
Nominal voltage24 V DC (-15%/+20%)
Distributed clocksyes
Current consumption from US120 mA
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical isolation500 V
Weightapprox. 200 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL (in preparation)
Housing data8 x M8, 4 x M12, ID switch
Dimensions (W x H x D)30 mm x 155 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3