The EL2612 output terminal has two relays, each featuring a change-over contact. The signal state of the EtherCAT Terminal is indicated by light emitting diodes. The EL2612 features potential-free contacts; the power contacts are not passed through.
Special features:
- Relay output
- 2 x change-over
- Suitable for ohmic loads
- potential-free
- no power contacts
Product status:
regular delivery
Product information
Technical data | EL2612 |
---|---|
Connection technology | relay output |
Number of outputs | 2 x change-over |
Nominal voltage | 125 V AC/30 V DC |
Load type | ohmic |
Distributed clocks | – |
Ohmic switching current | 0.5 A AC/2 A DC per channel |
Minimum permitted load | 10 µA at 10 mV DC with intact contact coating |
Inductive switching current | no data |
Lamp test, electronic ballast | – |
Current consumption E-bus | typ. 150 mA |
Electrical isolation | 500 V (E-bus/field potential) |
Current consumption power contacts | – |
Bit width in the process image | 2 outputs |
Operating cycles mech. (min.) | 1 x 108 |
Operating cycles electr. (min.) | 2 x 105 (1 A/30 V DC) |
Configuration | no address or configuration setting |
Special features | signal relay |
Weight | approx. 50 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL |
Housing data | EL-12-8pin | ES-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Ordering information | |
---|---|
EL2612 | EtherCAT Terminal, 2-channel relay output, 125 V AC, 30 V DC, 0.5 A AC, 2 A DC |
ES2612 | EtherCAT Terminal, 2-channel relay output, 125 V AC, 30 V DC, 0.5 A AC, 2 A DC, pluggable wiring |