IE4132 | Extension Box, 4-channel analog output, voltage, ±10 V, 16 bit, differential, M12

Image similar, may contain optional accessories
IE4132 | Extension Box, 4-channel analog output, voltage, ±10 V, 16 bit, differential, M12

IE4132 | Extension Box, 4-channel analog output, voltage, ±10 V, 16 bit, differential, M12

IP-Link interface
M12 I/O connection sockets
Signal status display
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
1 | Output +/-
2 | +24 V DC UP
3 | Output GND
4 | GNDP
5 | Shield
1 | +24 V DC US
2 | +24 V DC UP
3 | GNDS
4 | GNDP
Top view 
I/O connection 
Connector assignment 
IE4132 | Extension Box, 4-channel analog output, voltage, ±10 V, 16 bit, differential, M12

IE4132 | Extension Box, 4-channel analog output, voltage, ±10 V, 16 bit, differential, M12

The IE4132 analog output module generates analog output signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits, and is electrically isolated. If necessary, the output scaling can be altered.

Ground potential for the four output channels is common with the 24 V DC supply. The analog actuators are powered by the control voltage. The applied load voltage (which can be any value up to 30 V DC) is available for supply of the actuators.

Product status:

regular delivery

Product information

Technical dataIE4132
Number of channels4 analog outputs
Number of outputs4
Output connectionsM12, screw type
Signal current-10/0…10 V
Nominal voltage24 V DC (-15%/+20%)
Load> 5 kΩ
Resolution16 bit (incl. sign)
Conversion time< 4 ms
Measurement error/uncertainty< ±0.1% (relative to full scale value)
Actuator supplyfrom the auxiliary voltage UP
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Bit width in the process imageoutput: 4 x 16 bit data (4 x 8 bit control/status optional)
Electrical isolationchannels/control voltage: yes, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Current consumption from US (without sensor current)40 mA
Operating/storage temperature0…+55°C/-25…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing dataExtension Box
Dimensions (W x H x D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3