The ELX9410 power supply terminal is used to refresh the E-bus. Data is exchanged between EtherCAT Coupler and EtherCAT Terminals over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the corresponding coupler’s power supply unit. In configurations with a large number of ELX terminals it is possible to use the ELX9410 in order to increase the E-bus power supply to 1 A. The ELX9410 has a diagnostics function, which is indicated by LEDs and on the process image.
In addition, the ELX9410 is equipped with a fin that can be used to check whether the separation distance stipulated by IEC 60079-11 is observed. This enables the installation of an additional ELX9560 power supply terminal in order to continue an ELX terminal strand on the same DIN rail. Moreover, two ELX9410 terminals can be installed in direct succession to reach the required separation distance for continuing the same terminal strand with standard EtherCAT Terminals. In this way, it is possible to conveniently combine the transmission of intrinsically safe signals with all features of the EtherCAT Terminals.
Product status:
regular delivery
Product information
Technical data | ELX9410 |
---|---|
Technology | terminal supply |
Short-circuit proof | yes |
Input voltage | 24 V DC |
Input current | typ. 45 mA + (E-bus/4) |
Output voltage | 5 V for E-bus supply |
Max. output current | 1 A |
Diagnostics in the process image | yes |
Special features | E-bus refresh for ELX and EL terminals |
Weight | approx. 65 g |
Housing width | 12 mm |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/see documentation |
Approvals/markings | CE, UL, ATEX, IECEx, cFMus, CCC |
Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
Housing data | ELX-12-PWR |
---|---|
Design form | compact terminal housing with signal LED and plugged fin |
Material | polycarbonate, blue |
Dimensions (W x H x D) | 12 mm x 100 mm x 83 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Power contacts | no |
*s: solid wire; st: stranded wire; f: with ferrule