The analog EL3356-0030 input terminal enables direct connection of a resistor bridge or load cell in a 4- or 6-wire connection technology. The ratio between the bridge voltage UD and the supply voltage UREF is determined simultaneously in the input circuit and the final load value is calculated as a process value on the basis of the settings in the terminal. With automatic self-calibration (can be deactivated), dynamic filters and distributed clock support, the terminal with measuring cycles of 100 µs can be used for fast and precise monitoring of torque or vibration sensors.
The individual calibration certificate for each device, in accordance with ISO 17025 or DAkkS, depending on the device variant, can be downloaded here. These calibration certificates are issued for Beckhoff by an accredited service provider. Recalibration on request.
Product status:
regular delivery
Product information
Technical data | EL3356-0030 |
---|---|
Number of inputs | 2, for 1 resistor bridge in full bridge technology |
Distributed clocks | yes |
Measuring range UD | max. -25…+25 mV rated voltage |
Measuring range UREF | max. -12…+12 V rated voltage |
Internal resistance | > 200 kΩ (UREF), > 1 MΩ (UD) |
Supported nominal sensitivity | all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V |
Input filter limit frequency | 10 kHz low pass (-3 dB) |
Conversion time | 0.1…250 ms, configurable, max. 10,000 samples/s |
Conversion rate | 10,000…4 samples/s (0.1…250 ms conversion time) |
Power supply UV | up to 12 V DC from power contacts, dependent on sensor |
Resolution | 24 bit, 32 bit presentation |
Measurement error/uncertainty | < ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active |
Calibration certificate (analog) | externally calibrated |
Current consumption power contacts | depends on strain gauge supply, min. 1 mA |
Current consumption E-bus | typ. 280 mA |
Special features | self-calibration, quadruple averager, dynamic filters, fast data sampling |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Weight | approx. 60 g |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings | CE, UL, ATEX, IECEx |
Protect. rating/installation pos. | IP20/variable |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Ordering information | |
---|---|
EL3356-0030/000057324 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, high-precision, externally calibrated, ISO 17025 |