The EP6002-0002 serial interface module allows the connection of devices with an RS232 or RS422/RS485 interface. The module transmits the data in a fully transparent manner to the higher-level automation device. The data is transferred via the fieldbus using a simple handshake protocol. This does not have any effect on the protocol of the serial interface. The active serial communication channel functions independently of the higher-level bus system in full duplex mode at up to 115,200 baud, while a 864 byte receive buffer and a 128 byte send buffer are available.
The connector assignment depends on the interface. For each channel, RS232 or RS422/RS485 can be selected.
In conjunction with the TwinCAT Virtual Serial COM Driver (see TwinCAT Supplements – Communication) the EP6002-0002 can be used as a normal Windows COM interface.
Product status:
regular delivery
Product information
Technical data | EP6002-0002 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
Data transfer channels | 2 |
Interfaces | individually selectable from RS232, RS485, RS422 |
Data transfer rates | 300…115,200 baud; 9600 baud (8 bit, no parity, 1 stop bit) is preset |
Communication | TxD and RxD, full duplex |
Bit distortion | < 3% |
Cable length | RS232: max. 15 m; RS422/RS485: approx. 1000 m |
Data buffer | 864 bytes receive buffer, 128 bytes transmit buffer |
Sensor supply | +5 V DC, 20 mA each, electrically isolated |
Connection method | M12 socket, 5-pin, a-coded |
Number of channels | 2 (1/1), TxD and RxD, full duplex |
Number of digital inputs/outputs | – |
Nominal voltage | 24 V DC (-15%/+20%) |
Distributed clocks | – |
Current consumption from US | typ. 130 mA + sensor supply |
Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
Electrical isolation | 500 V |
Special features | easy integration of serial end devices |
Weight | approx. 165 g |
Operating temperature | -25…+60°C |
Storage temperature | -40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | 8 x M8, 4 x M12 |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |