DetachFixClose

Headquarters Australia
Beckhoff Automation Pty. Ltd.

Building 4, 163–179 Forster Road
Mount Waverley, VIC 3149, Australia

+61 3 9912 5430
info@beckhoff.com.au
www.beckhoff.com/en-au/

EPP2339-0703 | EtherCAT P Box, 16-channel digital combi, ID switch, 24 V DC, 3 ms, 0.5 A, IP20 connectorNew

The EPP2339-0703 EtherCAT P Box has 16 digital channels, each of which can be operated as input or output. It is not necessary to configure whether a channel is to be used as input or output. The input circuit is permanently connected to the output driver internally so that a set output is also automatically displayed in the input process image.

The inputs have a filter of 3.0 ms, the outputs process load currents of up to 0.5 A and are short-circuit proof and protected against polarity reversal. The sum current of all outputs is limited to 3 A. The connected sensors are supplied via an internal, short-circuit proof driver block with a total of 0.5 A for all sensors. The inputs and outputs are supplied from UP. The signal connection is established via spring-loaded connectors, optionally available in 1- and 3-pin versions.

 

The EPP2339-0703 has three additional hexadecimal ID switches. In this way, an individual address from 0...4095 can be set, allowing unique identification regardless of installation position, as required by some device profiles for certain industries, such as the semiconductor industry.

Product status:

product announcement

Product information

Technical dataDigital input
SpecificationEN 61131-2, type 1/3
Input filter3.0 ms
“0” signal voltage-3…+5 V (EN 61131-2, type 3)
“1” signal voltage11…30 V (EN 61131-2, type 3)
Input currenttyp. 3 mA
Sensor supplyfrom load supply voltage, max. 0.5 A, short-circuit proof in total
Technical dataDigital output
Load typeohmic, inductive, lamp load
Rated load voltage24 V DC (-15%/+20%)
Max. output current0.5 A per channel, individually short-circuit proof, ∑ 3 A
Switching timestyp. TON: 25 µs, typ. TOFF: 75 µs
Short-circuit currenttyp. 1.5 A
Technical dataGeneral
ProtocolEtherCAT
Bus interface2 x M8 socket, P-coded, shielded
Number of configurable IDs4096
Number of channels16 digital inputs or outputs
Input/output connectionsconnector with spring-loaded system
Auxiliary power currenttyp. 20 mA
Current consumption from UStyp. 100 mA
Electrical isolation500 V
Weightapprox. 200 g
Operating/storage temperature-25…+60°C/-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL (in preparation)
Housing data8 x M8, 4 x M12, ID switch
Dimensions (W x H x D)30 mm x 155 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3