The IE3112 analog input module handles signals in the range from 0/4 to 20 mA. The input current is digitized to a resolution of 16 bits (the default is 15 bits), and is transmitted, electrically isolated, to the higher-level automation device. The four input channels have differential inputs and possess a common, internal ground potential. The applied load voltage (which can be any value up to 30 V DC) is fed through to supply the sensor. The module is quite versatile, but default settings have been selected in such a way that in most cases it is not necessary to perform configuration. The input filter and associated conversion times can be set within a wide range; several data output formats may be chosen. If required, the inputs can be scaled differently. Automatic limit monitoring is also available. Parameterization may be carried out either via the fieldbus or using the KS2000 software tool through the Coupler Box configuration interface. The parameters are stored in the module.
Product status:
regular delivery
Product information
Technical data | IE3112 |
---|---|
Number of inputs | 4 |
Input connections | M12, screw type |
Signal voltage | 0/4…20 mA |
Internal resistance | 80 Ω measuring shunt |
Common-mode voltage UCM | max. 35 V |
Resolution | 16 bit |
Measurement error/uncertainty | < ±0.3% (relative to full scale value) |
Conversion time | 250 ms, configurable to 5 ms |
Nominal voltage | 24 V DC (-15%/+20%) |
Input filter | configurable |
Sensor supply | from load supply voltage UP |
Current consumption from US (without sensor current) | 55 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
Bit width in the process image | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Electrical isolation | channels/control voltage: 500 V, between the channels: no, control voltage/fieldbus: yes, via IP-Link |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |
Housing data | Extension Box |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2024 - Terms of Use