The compact KM2774 module enables direct connection of up to four AC motors with reversal of rotation direction and a further travel function. For each motor, three mutually locked Triac outputs with 230 V AC and up to 1.5 A are available. The outputs are protected against overload. An adjustable overcurrent limit protects the motor from damage. The typical control signals can be wired via 24 V inputs. Status and error messages are available via the fieldbus and via LED at the module.
Product status:
regular delivery (not recommended for new projects) | recommended alternative: KL2722
Product information
Technical data | KM2774 |
---|---|
Number of outputs | 4 x 3 make contacts |
Nominal voltage | 80…230 V AC |
Overcurrent limit | adjustable |
Signal input | 12 x 24 V DC |
Load type | ohmic, inductive |
Max. output current | 1.5 A per channel |
Rotating field frequency | 50 Hz |
Surge voltage protection | > 275 V AC |
Peak current | 40 A (16 ms), 3 A (30 s) |
Switch-off time | T/2 |
Residual voltage | max. 1.5 V |
Electrical isolation | 500 V (K-bus/field voltage), 3750 V AC (1 min.) |
Leakage current (OFF state) | typ. 0.8 mA, max. 1.5 mA |
Switching times | 0.1…10 ms, zero crossing |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 30 mA |
Bit width in the process image | 3 byte input/output |
Configuration | no address or configuration setting |
Dimensions (W x H x D) | 132 mm x 100 mm x 38 mm |
Weight | approx. 270 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE |